SPECIFICATIONS
Brand Name: NONE
DIY Supplies: Electrical
Electronic: No
High-concerned chemical: None
Model: SFR-SVG
OEM: available
Origin: Mainland China
Product name: Power factor correction SVG static reactive power generator static
Rated current: 100A
Semi-finishedproduct: No
certificate: ISO, CE, CCC
country of origin: Jiangsu, China
efficiency: ≥ 97%
frequency: 50-65Hz
function: reactive power compensation
rated voltage: 400V
response time: ≤ 5ms
show: LCD
standard: IEEE519
usage: Power distribution equipment









|
Input
|
||
|
System voltage
|
Line voltage 400V
|
|
|
System voltage range
|
±15%
|
|
|
Frequency
|
50Hz ±5%
|
|
|
Output and installation
|
||
|
Capacity specification
|
50kVar
|
|
|
Module type
|
Rack Mounted
|
|
|
Incoming way
|
Upper incoming/Back incoming
|
|
|
Performance
|
||
|
Harmonics filtering rate
|
≥90% (Within the range of the ordered capacity, and the load harmonic content is higher than 30% of the ordered capacity)
|
|
|
Harmonics filtering range
|
2nd ~51st harmonics(If you need to control the harmonic order of more than 25 times, you should write in the contract)
|
|
|
Full response time
|
≤5ms
|
|
|
Instantaneous response time
|
≤100us
|
|
|
Dynamic current
|
1.2 times the filter rated capacity output,1min
|
|
|
Protection
|
||
|
Overload protection
|
Automatic current limit at 100% rated output
|
|
|
Other protection
|
Over-voltage protection, under-voltage protection, over-temperature protection, over-current protection
|
|
|
Operation mode
|
||
|
Stand-alone operation
|
Support
|
|
|
Parallel operation
|
Conventionally support 8 sets, special requirements can be customized
|
|
|
Display and operation
|
||
|
Status display
|
Power / Operation / Fault LED indication
|
|
|
Module operation
|
Start/Stop/Restart
|
|
|
HMI
(Optional) |
Optional 7” (Hole size 215×152mm)
10” (Hole size 261×180mm) |
|
|
Communication
(RS485 interface) |
1 loop Modbus-RTU protocol external communication interface, Users can have access to the background system through this interface or HMI port
|
|
|
Environment condition
|
||
|
IP level
|
IP20(customized)
|
|
|
Operating environment temperature
|
-25℃~40℃
|
|
|
Storage/ transport temperature
|
-25℃~55℃
|
|
|
Work humidity
|
Relative humidity 5~95%,no condensation
|
|
|
Altitude
|
1000m and below(above 1000m, Every additional 100m / 1% derating)
|
|
|
Standard
|
IEEE519
|
|

































Reviews